Description
Description
Primary Current Injection Test Sets are used to loading, Calibration and testing of CT's bimetals relays, Protection relays etc. Mostly Primary Injection Test set are designed as per customer's specification. The Primary Injections Test sets are of 15 minutes ON/30Minutes OFF duty i.e. testing duty only. Loading transformers are design for continuous use for Temperature Rise or bus duct/Bus Bar etc. Optional accessories requirement may include cable termination, timer, Temperature Indicator, multiple contactor, individual Phase control etc. Equipments are Compact in nature. It is available in portable trolley type/stationery type model Amps. Optional digital/analogue timer. Main Transformer up to 25,000Amps.
Special Feature
Special Features
- Supplied up to 25000 Amps.
- Electronic Parameter Monitoring.
- Multiple safety interlocks for the operator.
- Rugged in construction for site application.
Accessories
Standard Accessories
- Interconnecting Control Cable if the unit is in two part.
- Trolley if the unit is in two part.
Optional Accessories
- Output cable.
- CT Clamp
- Canvas Cover.
Tech Details
Single Phase Primary Current Injection Test Set |
Sr. No. |
Parameters |
Description |
1 |
I/p Voltage |
220/230V Single phase or two phase 50/60HZ AC Supply |
2 |
O/p Current |
Up to 25000A |
3 |
Capacity |
Up to 100KVA |
4 |
Duty Cycle |
Intermittent or countinous |
5 |
Control |
1- The unit can be manual/motorized control for cuurent variation and push button controlled. 2- The unit can be microprocessor based complete with on board digitized panel. 3- The unit can be PLC based complte with computer, HMI memory, printer etc. for operation. |
6 |
Power Components |
1- Step down transformer : 1 No. double wound transformer shall be used for supplying high Current and low voltage for testing. 2 - Auto Transformer : 1 No. Motorized Auto Transformer shall be used for controlling the output voltage from zero to maximum to control the load Current. |
7 |
Metering |
1- Ampere meter : 1 No. Digital Ampremeter shall be provided with 0.5 classes CT to indicate the output current. The size of the amperemeter shall be 96 sq.mm, one in case of single phase unit. 2 - Voltmeter : A digital voltmeter with selector switch shall be provided to indicate the output voltage each phase/phase to phase, if required. 3 - Line On Indicator : Neon lamp indicators are provided for input indication. 4- Main ON/OFF switch : Two pole ON/OFF is provided for input ON &OFF. 5- Option for XCT current mesurement and input current measurement. |
8 |
Termination |
Output is brought on Copper bus-bars |
9 |
Control Panel |
(i) ON/OFF switch (ii) Separate Indiaction lamp (iii) Digital Output Ampere meter and Voltmeter. (iv) Knob / Push button for raising and lowering the output current. |
10 |
Regulating Transformer |
Will be suitable for Motorized operation having limit switches, lifting arrangement for Regulating Transformer and for the whole unit, Input & Output Indicators. Will be suitable for Motorized or manual operation having limit switches |
11 |
Step Down Transformer |
Shall be air cooled type. Primary winding having DCC insulation and secondary winding of bare copper strip. The unit shall be housed in a MS Sheet body supported an angle iron frame. Output shall be brought out on Copper bus- bar of electrolyte grade. |