Description
Description
Kilo Volt Meter (kV) meters used tomeasure the kilo volt value of an Instrument Transformer, CT/PT etc. The unit is used for higher value calibration with a wide range from 1% to 110%. Kilo Voltmeters are highly accurate, portable voltage measurement systems traceable to NABL standards. The Kilo meter series consists of a high voltage divider assembly, a precision readout device and interconnection leads. The battery operation makes the system completely portable for field testing while the precision divider assembly and readout device makes it suitable for laboratory use.
Special Features
Features
- Used to measure AC/DC voltage measurement / partial Discharge measurement from any High Voltage source such as AC HV test system, PT/CT power / distribution transformer.
- Available up to 800Kv.
- Variable Capacitance from 50pf to 1nf.
- Perform multiple measurements.
- DC measurement, AC peak, AC-RMS,True Value.
- Digital Read out.
- AC/DC Coupling.
- Battery or line power, Built in Self regulating battery charger.
- Light weight & portable divider.
Accessories
Standard Accessories
Optional Accessories
Tech Details
Kilo Volt Meter |
Sr. No. |
Parameters |
Description |
1 |
Maximum Capacity |
Up to 800kV |
2 |
Number of Sections |
One for each 200kV or one for 100kV depends on capacity |
3 |
Length of Section |
100kV - 0.75 meter 200kV - 1.25meter |
4 |
Capacitance of the unit |
Generally 200pF |
5 |
Measured Parameter |
Peak Voltage, RMS Voltage, DC Voltage and peak/ √2 |
6 |
Frequency Response (AC) |
AC 40 to 60HZ |
AC 40 to 200HZ |
7 |
Frequency Response (DC) |
Up to 1MHz |
8 |
Least Count |
0.1kV |
9 |
Enclosure |
FRP |